Reversing, 3ø Motor (Electric)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
  IMPORTANT:
  NOTES: A.
 B.
 C.
208 VAC AND 240 VAC ARE NOT THE SAME.  When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.  For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz
50 Hz
60 kW
208
3
181
*
250
250
230
3
167
*
200
200
240
3
159
*
200
200
380
  4**
100
*
125
125
400
  4**
95
*
125
125
416
  4**
92
*
125
125
460
3
83
*
125
125
480
3
80
*
100
100
575
3
66
*
100
100
72 kW
208
3
214
*
300
300
230
3
197
*
250
250
240
3
188
*
250
250
380
  4**
118
*
150
150
400
  4**
112
*
150
150
416
  4**
109
*
150
150
460
3
98
*
125
125
480
3
94
*
125
125
575
3
78
*
100
100
*
AWG Stranded Wire Type; size wire as per National Electrical Code or local codes.  (Motor lead wire is recommended.)
12/10/08
**
3-Wire is available.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label.  In the
case of 208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC AND 230/240 VAC ARE NOT THE SAME.  Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
IMPORTANT: 380, 400, and 416 volt dryers are built 4-wire only.  Customer must contact the
factory to special order 3-wire systems.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.