Exhaust Requirements
Layout
Whenever possible, install tumblers along an outside 
wall where duct length can be kept to a minimum, and 
make-up air can be easily accessed. Elbows and long 
vents tend to increase drying time. Construction must 
not block the airflow at the rear of the tumbler. Doing 
so would prevent adequate air supply to the tumbler’s 
combustion chamber.
Make-Up Air
A tumbler is forced air exhausted and requires 
provisions for make-up air to replace the air exhausted 
by the tumbler. 
IMPORTANT: Do not obstruct the flow of 
combustion and ventilation air.
Make-up air openings should be as close to the 
tumbler(s) as possible.
The required make-up air opening to the outside for 
each tumbler is:
144 square inches (928 sq. cm) for 25, 30 and 
35 pound tumbler models
288 square inches (1856 sq. cm) for T30 tumbler 
models
Make-up air openings with louvers will restrict 
airflow. The opening must be increased to compensate 
for area taken up by louvers.
Make-up air openings for a room containing 
tumbler(s) and/or gas fired hot water heater or other 
gravity vented appliances must be increased 
sufficiently to prevent downdrafts in any of the vents 
when all tumblers are in operation. Do not locate 
gravity vented appliances between tumbler(s) and 
make-up air openings. If it is necessary to duct make-
up air to the tumbler(s), increase the area of the 
ductwork by 25% to compensate for any restriction in 
air movement.
Venting
For maximum efficiency and minimum lint 
accumulation, tumbler air must be exhausted to the 
outdoors by the shortest possible route.
Proper sized exhaust ducts are essential for proper 
operation. All elbows should be sweep type. Exhaust 
ducts must be assembled so the interior surfaces are 
smooth, so the joints do not permit the accumulation 
of lint. DO NOT use plastic or thin foil flexible ducts. 
Use exhaust ducts made of sheet metal or other 
noncombustible material. Use duct tape or pop-rivets 
on all seams and joints. 
Verify that old ducts are thoroughly cleaned out before 
installing new tumbler.
NOTE: Exhaust ducts shall be constructed of sheet 
metal or other noncombustible material. Such 
ducts must be equivalent in strength and corrosion 
resistance to ducts made of galvanized sheet steel 
not less than 0.0195 inches (0.495 mm) thick.
Where the exhaust duct pierces a combustible wall, 
ceiling, floor or partition the opening must be sized per 
local codes. The space around the duct may be sealed 
with noncombustible material. Refer to 
Figure 9.
IMPORTANT: For best performance provide an 
individual exhaust duct for each tumbler. Do not 
install a hot water heater in room containing 
tumblers. It is better to have the water heater in a 
separate room with a separate air inlet.
A drying tumbler produces combustible 
lint. To reduce the risk of fire, the tumbler 
must be exhausted to the outdoors.
W057
To reduce the risk of fire and accumulation 
of combustible gases, DO NOT exhaust 
tumbler air into a window well, gas vent, 
chimney or enclosed, unventilated area 
such as an attic wall, ceiling, crawl space 
under a building, or concealed space of a 
building.
W059
WARNING
Improperly sized or assembled ductwork 
causes excess back pressure which 
results in slow drying, lint collecting in the 
duct, lint blowing back into the room, and 
increased fire hazard.
W355
WARNING