Exhaust Requirements
27
70420801 (EN)
Individual Venting
For maximum efficiency and performance, it is 
preferred to exhaust tumble dryer(s) individually to 
the outdoors.
IMPORTANT: At no point may the cross sectional 
area of installed venting be less than the cross 
sectional area of the exhaust outlet of the tumble 
dryer.
The exhaust duct must be designed so the static back 
pressure measured 12 inches (305 mm) from the 
exhaust outlet does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of the tumble dryer. 
NOTE: Static back pressure must be measured 
with the tumble dryer running.
The maximum allowable length of venting of the same 
diameter as the exhaust thimble is 14 feet (4.3 meters) 
and two 90° elbows or equivalent. If the equivalent 
length of a duct required for an installation exceeds the 
maximum allowable equivalent length, the diameter of 
a round duct must be increased by 10% for each 
additional 20 feet (6.1 meters). Cross section area of a 
rectangular duct must be increased by 20% for each 
additional 20 feet (6.1 meters). Refer to Table 4 to 
determine equivalent venting:
With the tumble dryer in operation, airflow at any 
point in the duct should be at least 1200 feet per 
minute (366 meters per minute) to ensure that lint 
remains airborne. If 1200 feet per minute (366 meters 
per minute) cannot be maintained, schedule monthly 
inspections and cleaning of the ductwork.
NOTE: The maximum length of a flexible metal 
duct must not exceed 7.87 ft. (2.4 m) as required to 
meet UL2158, claus 7.3.2A.
Manifold Venting
While it is preferable to exhaust tumble dryers 
individually to the outdoors, a main collector duct may 
be used if it is sized according to Figure 8. This 
illustration indicates minimum diameters, and should 
be increased if collector length exceeds 20 feet (6.1 
meters). Manifold duct may be rectangular in cross 
section, as long as area is not reduced. Provisions 
should be made for lint removal and cleaning of duct. 
Manifold duct must be tapered, as shown in Figure 6
Individual tumble dryer ducts must enter manifold 
duct at a 45° angle in the direction if airflow. 
NOTE: Never connect a tumble dryer duct at a 90° 
angle to a collector duct. Refer to Figure 6. Doing 
so will cause excessive back pressure, resulting in 
poor performance. Never connect two tumble 
dryer exhaust ducts directly across from each other 
at the point of entry to manifold duct.
Figure 6 
Exhaust system must be designed so static back 
pressure measured 12 inches (305 mm) from exhaust 
thimble does not exceed maximum allowable pressure 
specified on installation sticker on rear of tumble 
dryer. This must be measured with all tumble dryers 
running that are vented into collector.
With the tumble dryer in operation, airflow at any 
point in the duct should be at least 1200 feet per 
minute (366 meters per minute) to ensure that lint 
remains airborne. If 1200 feet per minute (366 meters 
per minute) cannot be maintained, schedule monthly 
inspections and cleaning of the ductwork.
Duct Diameter
Equivalent Length
of Rigid Straight Duct
10 in. (254 mm)
12 in. (305 mm)
14 in. (356 mm)
16 in. (406 mm)
18 in. (457 mm)
One 90° elbow = 11.6 ft. (3.5 m)
One 90° elbow = 14 ft. (4.3 m)
One 90° elbow = 16 ft. (4.9 m)
One 90° elbow = 18.7 ft. (5.7 m)
One 90° elbow = 21 ft. (6.4 m)
Equivalent Length (ft.) = 1.17 x Duct Diameter (in.)
Table 4 
Example: A 12 inch (305 mm) diameter duct’s 
equivalent length of 14 feet (4.3 meters) of duct and two 
90° elbows is:
Equivalent Length: = 14 ft. (4.3 m) + (2) 90° elbows
= 14 ft. (4.3 m) + 14 ft. (4.3 m) 
+ 14 ft. (4.3 m)
= 42 ft. (12.8 m)
T438I