Alliance Laundry Systems Drying Cabinet User Manual

Page of 53
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Exhaust Requirements
27
70304601
Manifold Venting
While it is preferable to exhaust tumblers individually 
to the outdoors, a main collector duct may be used if it 
is sized according to Figure 11. This illustration 
indicates minimum diameters, and should be increased 
if the collector length exceeds 14 feet (4.3 m) and two 
90° elbows. The diameter of a round duct must be 
increased by 10% for each additional 20 feet (6.1 m). 
Cross sectional area of a rectangular or square duct must 
be increased 20% for each additional 20 feet (6.1 m). 
Refer to Table 5 to determine equivalent ducting 
sizing. The collector duct may be rectangular or square 
in cross section, as long as the area is not reduced. 
Provisions MUST be made for lint removal and 
cleaning of the collector duct.
The vent collector system must be designed so the 
static back pressure measured 12 inches (305 mm) 
from the exhaust outlet does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of tumbler. Static back pressure must be 
measured with all tumblers vented into the collector 
operating.
NOTE: Never connect a tumbler duct at a 90° angle 
to the collector duct. Refer to Figure 10
. Doing so 
will cause excessive back pressure, resulting in poor 
performance. Never connect two tumbler exhaust 
ducts directly across from each other at the point of 
entry to the collector duct.
With the tumbler in operation, and both pockets 
running, airflow at any point in the duct should be at 
least 1200 feet per minute (366 meters per meter) to 
ensure that lint remains airborne. If 1200 feet per 
minute cannot be maintained, schedule monthly 
inspections and cleaning of the ductwork. 
Figure 10
T438I
T438i