Liebert 104 165 User Manual

Page of 44
Site Preparation
9
Figure 8
Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers
Figure 9
Piping connections for 6- and 8-fan Fan Speed Condensers
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-provided).
Support field piping separately
to avoid coil damage and loss
of charge.
Liquid
Line
Leaving
Liquid
Line
Hot Gas
Line
Entering
Hot Gas Line
See Detail A-A
Position elbow
to direct relief
valve downward
Inverted Traps (field-supplied)
to extend 8" (203mm) above
coil base
DPN001067
Rev. 0
Detail A-A
Metal clamp
Isolator
Access Valve (Hot Gas) on
Condensers (Typ. 2)
Inlet Connection
Upper Headers
(Typ.)
Entering
Hot Gas
Line
Leaving
Liquid Line
Condenser
Connections,
Typical
Fasten liquid and hot gas lines
to leg using flat surface clamps
with isolators (field-supplied).
See
Detail
A-A
DPN000668
Rev. 01
Inverted traps (field-supplied)
to extend above base of coil by
a minimum of 7-1/2" (190mm).
Detail A-A
Metal
Clamp
Isolator