Alternate installations for close clearances
Venting systems come in many varieties. Select the type best for 
your installation. Two close-clearance installations are shown. 
Refer to the manufacturer’s instructions.
A
B
A. Over-the-top installation (also available with one offset elbow)
B. Periscope installation
NOTE: The following kits for close clearance alternate 
installations are available for purchase. To order, please see 
 
the “Assistance or Service” section.
Over-the-Top Installation:
 
Part Number 4396028
Periscope Installation (For use with dryer vent to wall vent 
mismatch):
Part Number 4396037 - 0" (0 mm) to 18" (457 mm) mismatch
Part Number 4396011 - 18" (457 mm) to 29" (737 mm) 
mismatch
Part Number 4396014 - 29" (737 mm) to 50" (1270 mm) 
mismatch
Special provisions for mobile home installations
The exhaust vent must be securely fastened to a noncombustible 
portion of the mobile home structure and must not terminate 
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path
Select the route that will provide the straightest and most 
direct path outdoors. 
Plan the installation to use the fewest number of elbows and 
turns. 
When using elbows or making turns, allow as much room 
 
as possible. 
Bend vent gradually to avoid kinking. 
Use the fewest 90° turns possible.
Determine vent length and elbows needed for best 
drying performance
Use the following Vent system chart to determine type of vent 
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified in 
the Vent system chart. Exhaust systems longer than those 
specified will:
Shorten the life of the dryer.
Reduce performance, resulting in longer drying times and 
increased energy usage.
The Vent system chart provides venting requirements that will 
help to achieve the best drying performance.
Vent system chart
NOTE: Side and bottom exhaust installations have a 90º turn 
inside the dryer. To determine maximum exhaust length, add one 
90º turn to the chart.
Number of 
 
90º turns 
 
or elbows
Type of
 
vent
Box or 
 
Louvered 
 
hoods
Angled
 
hoods
0
Rigid metal
64 ft (20 m)
58 ft (17.7 m)
1
Rigid metal
54 ft (16.5 m) 
48 ft (14.6 m)
2
Rigid metal
44 ft (13.4 m)
38 ft (11.6 m)
3
Rigid metal
35 ft (10.7 m)
29 ft (8.8 m)
4
Rigid metal
27 ft (8.2 m)
21 ft (6.4 m)
Install Vent System
1. Install exhaust hood. Use caulking compound to seal exterior 
wall opening around exhaust hood.
2. Connect vent to exhaust hood. Vent must fit inside exhaust 
hood. Secure vent to exhaust hood with 4" (102 mm) clamp.
3. Run vent to dryer location. Use the straightest path possible. 
See “Determine vent path” in “Plan Vent System.” Avoid 90º 
turns. Use clamps to seal all joints. Do not use duct tape, 
screws, or other fastening devices that extend into the 
interior of the vent to secure vent. Items sticking through the 
vent can catch lint.