CSB HR1234W Leaflet

Page of 2
Cells Per Unit
6
Voltage Per Unit
12
Capacity
34W @ 15min-rate to 1.67V per cell @25 (77 )
Weight
Approx.
2.5 kg(5.51 lbs)
Maximum Discharge Current
100/130A(5sec)
Internal Resistance
Approx. 19 m
Operating Temperature Range
Nominal Operating Temperature Range
25
3 (77
5 )
Float Charging Voltage
13.5 to 13.8 VDC/unit Average at 25 (77 )
Recommended Maximum Charging
3.4A
Current Limit
Equalization and Cycle Service
14.4 to 15.0 VDC/unit Average at 25 (77 )
Self Discharge
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
F1/F2-Faston Tab187/250
Container Material
ABS(UL 94-HB/File E50263)*Flammability resistance of
(UL 94-V0/File E88637) can be available upon request.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 (  5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
Constant Power Discharge Characteristics Unit:W (25
,77 )
Constant Current Discharge Characteristics Unit:A (25
,77 )
HR 1234W
12V 34W
Specification
Powered by
HR 1234W is specially designed for high efficient
discharge application. Its characteristics are high energy
density, small footprint and high discharge efficiency. It can
be used for more than 260 cycles at 100% discharge in cycle
service, up to 5 years in standby service.
Width (W)
Dimensions : 
Unit: mm (inch)
Overall Height (H)
Container height (h)
Length (L)
100±1 (3.94±0.04)
94±1 (3.7±0.04)
151±2 (5.94±0.08)
65±1 (2.56±0.04)
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
73.8
49.2
36.8
29.7
25.4
18.5
14.6
10.5
5.99
4.25
1.67V
65.8
44.8
34.4
28.2
24.2
17.8
14.1
10.3
5.86
4.15
1.70V
62.2
42.9
33.3
27.5
23.6
17.4
13.8
10.1
5.80
4.11
1.75V
56.3
39.8
31.6
26.2
22.7
16.8
13.5
9.90
5.69
4.05
1.80V
50.3
36.4
29.7
24.9
21.7
16.2
13.1
9.66
5.60
3.99
1.85V
43.3
32.9
27.6
23.5
20.7
15.6
12.7
9.39
5.50
3.92
F.V/Time
2MIN
4MIN
6MIN
8MIN
10MIN
15MIN
20MIN
30MIN
60MIN
90MIN
1.60V
706
506
395
328
286
211
169
124
71.7
50.8
1.67V
645
470
376
315
276
205
165
121
70.5
50.1
1.70V
618
454
366
308
270
202
163
120
70.0
49.6
1.75V
571
426
350
296
260
196
160
118
69.0
49.0
1.80V
524
400
333
285
250
191
156
116
68.1
48.3
1.85V
478
376
316
273
241
186
152
114
67.0
47.7
RA0911
CSB-manufactured
VRLA 
batteries are UL-
recognized components
under UL924 and UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
 
(http://www.csb-battery.com) 
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified