Renesas rl78 User Manual

Page of 1004
 
RL78/G1A 
 
CHAPTER  11   A/D  CONVERTER 
R01UH0305EJ0200  Rev.2.00 
 
 
367  
Jul 04, 2013 
11.3.10  A/D test register (ADTES) 
This register is used to select the + side reference voltage or 
− side reference voltage for the A/D converter, an analog 
input channel (ANIxx), the temperature sensor output voltage, or the internal reference voltage (1.45 V) as the target for 
A/D conversion.  When using as the A/D test function, set as follows. 
• For zero-scale measurement, select the 
− side reference voltage as the target for conversion. 
• For full-scale measurement, select the + side reference voltage as the target for conversion. 
The ADTES register can be set by an 8-bit memory manipulation instruction. 
Reset signal generation clears this register to 00H. 
 
Figure 11-14.  Format of A/D Test Register (ADTES) 
 
Address: F0013H  After reset: 00H  R/W 
Symbol 
7 6 5 4 3 2 1 0 
ADTES 
0 0 0 0 0 0 
ADTES1 
ADTES0 
 
ADTES1 
ADTES0 
A/D conversion target 
0 0 
ANIxx/temperature sensor output voltage
Note
/internal reference voltage (1.45 V)
Not
e
  
(This is specified using the analog input channel specification register (ADS).) 
1 0 
− side reference voltage (Setting at ADREFM bit of ADM2 register) 
+ side reference voltage (Setting at ADREFP1, ADREFP0 bits of ADM2 register) 
Other than above 
Setting prohibited 
 
Note  Temperature sensor output/internal reference voltage (1.45 V) can be used only in HS (high-speed 
main) mode.  For detail, see Figure 24-3  Format of User Option Byte (000C2H/010C2H)
 
Caution  For details of the A/D test function, see CHAPTER 22  SAFETY FUNCTIONS. 
<R> 
<R>