Emerson AC4 User Manual

Page of 89
System and Control Options
Liebert
®
 AC4
34
7.6
Setup System - Setup Outputs
The Liebert AC4 has four outputs that may be configured individually. These outputs correspond to 
the four numbered inputs. For example, Device_1 is the unit connected to Input 1 and to Output 1. 
The output name is the same as the input name, as described in 
7.3.1 Change Label (Name of Input).
To configure an output:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
 to
 
choose System and 
Control, then press Enter ↵ (see 7.1 Login for help).
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
 to
 
choose 
Setup System, then press Enter ↵.
Select an Output to Configure
• From the Setup System Menu, shown at right, use the arrows
↑↓
 to
 
choose Setup Outputs and press Enter ↵.
• From the Select Output Menu, choose an output—for example, 
Device_1—and press Enter ↵.
Table 17 shows digital output features and their default settings: you 
may define an output as normally open or normally closed, set the device’s mode—operating, standby 
or not used—and specify whether to disable the device when an alarm occurs.
Use the steps following Table 17 to change the default settings for any digital output.
7.6.1 Define Output as Normally Open or Normally Closed
Each output may be set up as Normally Open (NO) or Normally Closed 
(NC). The default setting for all output points is NO (Normally Open).
• From the Setup Outputs Menu, shown at right, use the arrows
↑↓
 
to
 
choose Norm Open/Close and press Enter ↵.
• To change the normal state for this output, use the arrows
↑↓
 to
 
choose the state:
• NO (Normally Open)
• NC (Normally Closed)
• Press Enter ↵.
Table 17
Default settings - digital outputs
Feature
Default
Other Options
NORM OPEN/CLOSE
NO (Normally open)
NC (Normally closed)
MODE
Outputs 1-3:
Output 4:
OP (Operating)
ST (Standby)
OP (Operating)
ST (Standby)
NU (Not Used)
IN ALARM
E (Enable)
D (Disable)
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES
↑↓=NEXT
=SELECT
> SETUP OUTPUTS
SETUP SYSTEM INFO
SETUP OPERATION 
Select Output Menu
SELECT OUTPUT
> DEVICE_1  NO-OP-E
DEVICE_2  NO-ST-E
↑↓=NEXT
=SELECT
DEVICE_3  NO-NU-D
DEVICE_4  NO-NU-D
Setup Outputs Menu
SETUP DEVICE_1
> NORM OPEN/CLOSE: NO
MODE: OPERATING
↑↓=NEXT
=SELECT
IN ALARM: ENABLE
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
↑↓=NO/NC
=END