Omron FQM1-MMP21 User Manual

Page of 414
124
Serial Communications
Section 6-1
6-1
Serial Communications
The FQM1 supports the following serial communications functions. 
Protocol
Connections
Description
Ports
Peripheral
RS-
232C
RS-
422A
 Host Link
Host computer or 
OMRON PT (Programmable Terminal)
Various control commands, 
such as reading and writing 
I/O memory, changing the 
operating mode, and force-
setting/resetting bits, can be 
executed by sending Host 
Link (C-mode) commands or 
FINS commands from the 
host computer to the Coordi-
nator Module.
Use Host Link communica-
tions to monitor data, such as 
status trace data, or to send 
data, such as operating con-
ditions information, to the 
FQM1.
 OK
 OK
Not al-
lowed
No-protocol
Communicate with general-
purpose devices connected 
to the RS-232C port without 
a command–response for-
mat. The TXD(236) and 
RXD(235) instructions are 
executed from the program to 
transmit data from the send 
port or read data at the 
receive port. The frame 
headers and end codes can 
be specified.
Not 
allowed
OK
Not al-
lowed
1:N NT Link
(The 1:N NT 
Link commu-
nications are 
used even 
for 1:1 con-
nections.)
Data can be exchanged with 
PTs without using a commu-
nications program in the 
Coordinator Module.
OK
OK
Not al-
lowed
Serial PLC 
Link Slave
Up to ten words per Module 
can be shared with up to 
eight Coordinator Modules 
as slaves using a CJM1 CPU 
Unit as the maser.
An RS-422A Converter can 
be connected to the RS-
232C port on each Coordina-
tor Module to communicate 
via RS-422A/485, or one 
Coordinator Module can 
communicate via an RS-
232C connection to the 
CJ1M master.
The Serial PLC Links can 
also include PTs as slaves 
via NT Links (1:N) combined 
with Coordinator Modules.
Not 
allowed
OK
Not al-
lowed
Monitor and 
set parameters
Host computer
or
OMRON PT 
(Programmable 
Terminal)
General-purpose 
external device
OMRON PT
(Programmable Terminal)
FQM1
FQM1
FQM1
RS-422A/485
RS-232C
CJ1M CPU Unit
Master
CJ1W-CIF11 
connected to 
RS-232C port 
(See note.)
For NS-
series PT: 
NS-AL002
8 Units max.
CJ1M CPU Unit
Master