Omron FQM1-MMP21 User Manual
218
Analog Input Functions
Section 7-9
7-9-4
Related Areas and Settings
System Setup
Tab page
Function
Settings
Time when setting
becomes effective
Analog Input/
Output
Output
Both inputs
and outputs
and outputs
Input
method
method
0 hex:
END refresh
1 hex:
Immediate refresh (Refresh with PRV(881).)
At power ON and
start of operation
start of operation
Output
method
method
0 hex:
END refresh
(Content of A560 and A561 is output as
analog output after execution of END
instruction.)
(Content of A560 and A561 is output as
analog output after execution of END
instruction.)
1 hex:
Immediate refresh
(Analog output when SPED(885) or
ACC(888) is executed. A560 and A561
used for monitoring.)
(Analog output when SPED(885) or
ACC(888) is executed. A560 and A561
used for monitoring.)
At power ON and
start of operation
start of operation
Inputs
Input range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V
02 hex: 1 to 5 V (4 to 20 mA)
03 hex: 0 to 5 V
At power ON
Outputs
Output
range
range
00 hex:
−10 to 10 V
01 hex: 0 to 10 V
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Disable outputs (See note.)
02 hex: 1 to 5 V
03 hex: 0 to 5 V
5A hex: Disable outputs (See note.)
Note Outputs can be disabled to shorten the I/O
refreshing time or reduce the Motion Control
Module’s power consumption.
Module’s power consumption.
At power ON
Output stop
function
function
0 hex:
Clear outputs
1 hex:
Hold outputs
2 hex:
Maximum value
Outputs
Output
range
range
These parameters have the same settings as output
1, above.
1, above.
Output stop
function
function