Communication Manager Maintenance-Object Repair Procedures
1006 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Red Alarm Inquiry Test (#140)
DS1 Interface circuit pack raises a Red alarm when the framing pattern of the incoming DS1 bit 
stream has been lost. The Red Alarm Inquiry test checks the framing status of a DS1 Interface 
circuit pack. DS1 Interface circuit pack takes 3 seconds to recognize and report a Red alarm 
and 10 seconds to recognize and report the resolution of a Red alarm.
When the DS1 Interface circuit pack detects a Red alarm, the circuit pack will transmit a Yellow 
alarm to the remote DS1 endpoint and send a RED ALARM message to the maintenance 
software. After the Red alarm is confirmed, the maintenance software places all trunks of the 
circuit pack into the out-of-service state. The inquiry test will be run every 10 minutes until the 
Red alarm is cleared.
1795
FAIL
The DS1 Interface circuit pack detects a Payload Loopback Alarm (PLB). If 
the DS1 Interface circuit pack connects to a leased T1 facility, call the 
vendor of the T1 carrier to diagnose the remote DS1 endpoint. If the DS1 
Interface circuit pack connects directly to another DS1 board, call the 
system technician of the remote switch to diagnose the DS1 endpoint.
 
PASS
Remote DS1 endpoint is in-service. Neither a Blue alarm nor a Line 
Loopback alarm nor a Payload Loopback alarm is detected in the DS1 
Interface circuit pack.
0
NO 
BOARD
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an 
incorrect board is inserted, or an insane board is inserted.
1. Verify that the board’s translations are correct. Use add ds1 
location to administer the DS1 interface if it is not already 
administered.
2. If board was already administered correctly, check the error log to 
determine whether the board is hyperactive. If so, the board was shut 
down. Reseating the board will re-initialize it.
3. If the board was found to be correctly inserted in step 1, enter 
busyout board.
4. Enter reset board
5. Enter release board
6. Enter test board long
This should re-establish the link between the internal ID and the port.
Table 345: Test #139 Blue Alarm Inquiry Test  (continued)
Error 
Code
Test 
Result
Description / Recommendation
 3 of 3