Avaya 03-300430 User Manual
Communication Manager Maintenance-Object Repair Procedures
1214 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
1139
ABRT
The packet bus in the PN where this EI board resides has a major alarm
against it. This test needs to use the alarmed PN’s packet bus.
against it. This test needs to use the alarmed PN’s packet bus.
1. Enter display alarms and display errors and resolve any
PKT-BUS alarms.
2. Retry the command.
1141
ABRT
The Packet Interface circuit pack is out of service.
1. See
1144
ABRT
The PN’s packet bus has a major alarm against it. This test needs to use
the alarmed PN’s packet bus.
the alarmed PN’s packet bus.
1. Enter display alarms and display errors and resolve any
PKT-BUS alarms.
2. Retry the command.
1394
ABRT
The EI board is out of service and the test cannot be run. This condition is
due to a change in the EI board’s ability to communicate with the EI or SNI
circuit pack on the other end of the fiber.
due to a change in the EI board’s ability to communicate with the EI or SNI
circuit pack on the other end of the fiber.
1. Run Test #237 and check the Error Log for EXP-INTF Error Type 1281.
If Error Type 1281 is present or if Test #237 fails, see repair procedures
for Test #237, in
for Test #237, in
1395
ABRT
This test cannot be run on an EI circuit pack if it is part of the B-side PNC
and duplicated PNC is not enabled.
and duplicated PNC is not enabled.
1. If this test needs to run on this EI circuit pack, enable PNC with change
system-parameters duplication.
2. Use set pnc lock to prevent the system from doing a PNC
interchange.
3. Repeat this test.