EXP-INTF (Expansion Interface Circuit Pack)
Issue 1 June 2005
1231
 
2000
ABRT
Response to the test request was not received within the allowable time 
period.
1. Rerun the test at 1-minute intervals up to 3 times.
2100
ABRT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 3 times.
9999
ABRT
EI circuit pack reset successfully. Could not perform initialization test 
results query because link to PN is not up.
1. Execute release board PCSS. Wait one minute. Enter display 
error. If you see Error Type 2049 logged against this EI circuit pack, 
then the EI Test has failed with an error code equal to the aux data of 
this entry. Otherwise, the initialization tests have passed.
12000
ABRT
EI circuit pack reset successfully. Response to the initialization test results 
query was not received within the allowable time period.
12100
ABRT
EI circuit pack reset successfully. System resources required to run 
initialization test are not available.
1. Retry the command at 1-minute intervals up to 3 times.
12026
ABRT
EI circuit pack reset successfully. It responded with an unknown reply to 
the query for the results of its initialization tests.
1. Retry the command at 1-minute intervals up to 3 times.
2. If the test continues to abort, replace the circuit pack or transceiver.
1
FAIL
The EI did not successfully reset.
1. If the EI circuit pack is in the PN, the PN’s Maintenance board may be 
holding the EI circuit pack reset. Attempt to rectify this condition by 
executing test maint P long on the Maintenance board in the 
same PN.
2. If step 1 was not successful in releasing the EI circuit pack, temporarily 
remove the PN’s Maintenance circuit pack.
3. Enter reset board PCSS.
4. If reset continues to fail, replace circuit pack.
5. Insert PN’s Maintenance circuit pack if it was removed.