EXT-DEV ADMIN? Y (External Device Alarm)
Issue 1 June 2005
1247
 
Error Log Entries and Test to Clear Values
Note:
Note:
The loss of -48 volt power prevents detection of an external device alarm. 
AC-POWER, CARR-POW, and DC-POWER alarms could indicate the loss of the 
external device alarm -48 volt power source. ALARM-PT alarms may also 
indicate a loss of power. When analog line ports are administered as analog line 
external device alarms loss of -48 volts prevents detection of an external device 
alarm.
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when inspecting errors in the 
system. For example, by clearing error codes associated with the Battery & External Device 
Alarm 
test (#120), you may also clear errors generated from other tests in the testing sequence.
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
0
0
Any
Any
Any
test eda-external-device-alrm 
physical-location r 2 | 6
1 or 5
Any
External Device 
Alarm test (#120)
Any
OFF
test eda-external-device-alrm 
physical-location r 2 | 6
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
D/ND
1
1. D = Destructive; ND = Nondestructive
External Device Alarm test (MAJOR port) (#120)
X
X
ND
External Device Alarm test (MINOR port) (#120)
X
X
ND
External Device Alarm test (WARNING port) (#120)
X
X
ND