Communication Manager Maintenance-Object Repair Procedures
1252 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Notes:
a. The fiber is in frame, but no communication exists to the neighbor.
b. This is the normal state for an active PN EI circuit pack that is also the bus master 
(expansion Archangel) in the PN.
c. This is the normal state for an active EI circuit pack that is not the bus master (expansion 
Archangel) for a PN. This applies only in the direct connect configuration where the EI 
circuit pack in a PN connects via a fiber link to an EI circuit pack in the other PN. This state 
also applies for an active EI circuit pack located in the PN.
d. This is the normal state for a standby expansion Interface circuit pack in the PN.
For more details about how the EI circuit pack error codes relate to the LED states, see 
Notes:
a. A Fiber is out of frame or a fiber loss-of-signal condition exists.
b. DS1 converter/fiber endpoint communication is down.
c. The DS1 channel is down between the two DS1 converters in the DS1 converter complex.
Table 429: Expansion Interface Circuit Pack Amber LED Flashing Codes
Condition
LED on
LED off
Fiber Out-of-Frame
0.1 second
0.1 second
In frame-No Neighbor (
0.5 second
0.5 second
Expansion Interface Active (
)
2 second
0.2 second
Expansion Interface Active (
Solid on
Never off
Expansion Interface Standby (
)  Never on
Solid off
Table 430: DS1 Converter Amber LED Flashing Codes
Condition
LED on
LED off
Fiber out of Frame (
0.1 second
0.1 second
In frame, fiber channel is down (
0.5 second
0.5 second
In frame, DS1 channel down (
)
1 second
1 second
DS1 converter, no response from media server (
)
2 second
0.2 second
DS1 converter active
Solid on
Never off
DS1 converter standby
Never on
Solid off