FIBER-LK (Fiber Link)
Issue 1 June 2005
1287
 
When an EI endpoint is reset, the Expansion Interface Reset test (#336) is executed. When an 
SNI endpoint is reset, the SNI Reset test (#761) is executed. These tests are described in the 
EXP-INTF and SNI-BD sections.
This test starts the other reset test mentioned above and returns PASS without waiting for the 
results of the other reset test. For a better indication of how the other reset tests are running, 
use reset board location on each individual fiber link endpoint.
Failure Audit (#777)
This test is nondestructive.
This test queries the SNI(s) on the fiber link for any existing failures and any unacknowledged 
cleared failure messages. Each failure generates an error and alarm entry against SNI-BD, 
SNI-PEER, or FIBER-LK. An unacknowledged cleared failure message is a message the SNI 
circuit pack sent to software indicating a previous failure is now gone and the SNI circuit pack 
did not receive a message from software indicating that the failure message was received by 
software.
If no failures are detected by the SNI circuit pack, this test will pass.
If this test reports failures, the results screen for test fiber-link shows FAIL with no FAIL 
code. The error log must then be displayed via display errors with category PNC to view 
SNI-BD and FIBER-LK errors and display errors with category PNC-PEER to view 
SNI-PEER errors.
Table 441: Test #768 Fiber Link Reset Test 
Error 
Code
Test 
Result
Description / Recommendation
1703
ABRT
Both fiber endpoints are in the hardware path for INLs to their respective 
switch node carriers and, thus, cannot get a response from this test 
because the INLs response should come on will go down as a result of the 
reset.
1. Reset the individual fiber-link endpoints via reset board.
2500
ABRT
Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
PASS
The reset of both fiber endpoints successfully completed.