PDMODULE (Processor Data Module)
Issue 1 June 2005
1765
 
5
ABRT
Ringer update aborted (data module not in the in-service state)
1. Verify that the data module is powered (power LED on).
2. Make sure data module is connected to the building wiring, check for 
faulty wiring, check for faulty data module.
3. Retry the command at 1-minute intervals up to 5 times.
4. Replace the Data Module and repeat the test.
5. If the test continues to abort, replace the Digital Line circuit pack and 
repeat the test.
6
ABRT
Data module translation update aborted.
1. Verify the data module is connected to the PBX.
2. Retry the command at 1-minute intervals up to 5 times.
1000
ABRT
System resources required to run this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
1392
ABRT
This port is currently a TTI port and the test will not execute on it.
1. Verify that the port is a TTI port using display port, where the 
display shows that the port is a TTI port, or list config, where 
the display shows a t for the port.
2. If list config or display port indicate that the port is not a TTI 
port, escalate the problem. If both commands indicate that the port is 
a TTI port, the abort is correct, and no action is necessary.
2000
ABRT
Response to the test was not received within the allowable time period.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
PASS
Data Module audits passed. This digital port circuit pack is functioning 
properly.
1. If complaints still exist, investigate by using other port tests and by 
examining the data module options, wiring, and connections.
Table 653: Test #17 Data Module Audits Test  (continued)
Error
Code
Test
Result
Description / Recommendation
 2 of 2