Communication Manager Maintenance-Object Repair Procedures
1826 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
1373
ABRT
Could not establish the link loop around link to run this test.
1. Retry the command at 1-minute intervals up to 3 times.
2060
ABRT
Packet link’s bus went down during maintenance loop-around test.
1. Retry the command at 1-minute intervals up to 5 times.
2. If there are errors associated with the packet bus, see 
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABRT
Response to the test request was not received within the allowable time 
period.
1. Retry the command at 1-minute intervals up to 3 times.
2500
ABRT
Internal system error
1. Retry the command.
NO 
BOARD
The IPSI circuit pack’s Packet Interface module is assigned but is not 
detected as being physically present.
1. If the IPSI circuit pack is present, replace it.
2. If the IPSI circuit pack is not present, insert a TN2312AP IPSI circuit 
pack in the assigned slot, and rerun the test.
Table 671: Test #886 Maintenance Loop-Around Test  (continued)
Error 
Code
Test 
Result
Description / Recommendation