POWER
Issue 1 June 2005
1875
 
4
FAIL
The battery is currently being charged.
1. After 30 hours, the battery should be fully charged, and this error 
should clear.
2. If after 30 hours the battery is still in the high charge rate, an alarm 
will be raised. Use display errors to see the Error Log, and 
select the category “environs” to show only environment-related 
errors. Look for POWER errors of type 257. The first occurrence of 
this error indicates the time when the battery started charging. Use 
this time as the starting point to determine whether the battery has 
been charging for 30 hours. If so, then replace the battery and 
battery charger.
!
CAUTION:
CAUTION:
 Read the section, 
on page 1870 before proceeding.
3. Rerun the test. If the test still fails, then the PN’s MAINT 
(Maintenance) circuit pack could be reporting this condition 
incorrectly. There are failures that can occur on the PN’s 
Maintenance circuit pack that will not be detected by their 
respective maintenance, but which will cause many, if not every, 
environment test to fail. If many environment tests are failing, the 
suspect circuit pack, depending on the system configuration, 
should be replaced and the test rerun. Resolve every alarm on 
these MOs, and rerun the test.
6
FAIL
This indicates that Error Codes 2 and 4 occurred. Refer to these 
descriptions. Also, refer to this test’s description for Error Code 14.