Avaya 03-300430 User Manual

Page of 2574
Communication Manager Maintenance-Object Repair Procedures
1878 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
Battery and Charger for DC-Powered Systems
Note:
Note:
This MO applies to the J58890CE and the J58890CH-1 with large battery 
holdover.
This MO represents the battery backup unit found in AC-powered multicarrier cabinets. 
Because the system does not recognize the type of external power, this MO exists in 
DC-powered multicarrier cabinets but serves no functional purpose. In such cabinets, every 
POWER test should always pass or abort, and no POWER alarms should be raised.
S8700 Multi-Connect systems support two different types of PN cabinets: multicarrier and 
single-carrier. Both cabinet types may be powered by either AC or DC external power source. 
Environmental maintenance differs according to cabinet type and external power supply.
Error Log Entries and Test to Clear Values
Notes:
a. Error Type 0: run the short test sequence first. If every test passes, run the long test 
sequence. Refer to each test’s description, and follow its procedures.
b. Error Type 3840: this error is valid only for AC-powered multicarrier cabinets with battery 
backup. For DC-powered cabinets, ignore the error; it cannot be cleared.
MO Name in 
Alarm Log
Alarm
Level
Initial SAT Command to Run
Full Name of MO
POWER
MIN
test environment UU 
1
1. UU is the cabinet number indicated in the PORT field from the Alarm or Error Log.
Battery and Battery Charger
Table 685: Battery and Battery Charger Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
0 (
0
Any
Any
Any
test environment 
UU sh r 1
1
Any
Battery and Battery Charger 
Query (#5) (Error Code 8)
MIN
ON
test environment 
UU s r 1
257
Any
Battery and Battery Charge 
test (#5) (Error Code 4)
MIN
ON
test environment 
UU s r 1
769
Any
Battery and Battery Charger 
Query (#5) (Error Code 2)
MIN
ON
test environment 
UU s r 1
) 1005,
1028
Associated Battery and 
Battery Charger Query (#5)
test environment 
UU s r 1