Communication Manager Maintenance-Object Repair Procedures
1892 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
4
FAIL
The -48V is out of tolerance.
1. Use the status environment command to check the voltages: - 
48V (+/- 8%) (- 44.2 to 51.8 V) 
2. If redundant power supplies are present, there may be a problem 
with the backplane. Verify that each power supply can detect the 
problem by using the recycle carrier command, specifying the 
slot number of the power supply to be shut down. Refer to the notes 
and cautions for this command in Maintenance Commands 
Reference (03-300191)
 before executing the recycle carrier 
command.
3. Replace the power supply.
4. If the problem persists, check the backplane for shorts.
8
FAIL
The fan voltage is out of tolerance.
1. Use the status environment command to check the voltages: 
+12/14 V   (+11.4 to +15 V)
2. If redundant power supplies are present, there may be a problem 
with the backplane. Verify that each power supply can detect the 
problem by using the recycle carrier command, specifying the 
slot number of the power supply to be shut down. Refer to the notes 
and cautions for this command in Maintenance Commands 
Reference (03-300191) before executing the recycle carrier 
command.
3. Replace the power supply.
4. If the problem persists, check the backplane for shorts.
PASS
The power supply voltage test passes.
NO
BOARD
Power supply is administered but not detected.
1. Verify that the power supply is plugged in.
2. Replace the power supply.
1. The values of these failure codes might be added together. For example, a value of 3 indicates that both 
the +5V and the -5V are out of tolerance or a value of 15 indicates that all four voltages are out of 
tolerance.
Table 690: Test #1536 power supply voltage  (continued)
Error
code
Test
result
Description and recommendation