PS-RGEN (Power supply ring generator)
Issue 1 June 2005
1917
 
4
FAIL
There is an internal fault in the ring generator.
1. Run test board location
2. If the test continues to fail replace the power supply.
8
FAIL
The ring generator is off by command.
1. Run test board location
2. If the test continues to fail replace the power supply.
16
FAIL
The ringer on the primary power supply is not active.
1. Run test board location
2. If the test continues to fail replace the power supply.
32
FAIL
There is no ringing voltage on the backplane.
1. Run test board location
2. If the test continues to fail replace the power supply.
64
FAIL
Duplicated power supplies only. Unable to execute the ring test, because 
the power supply being tested has its ringer turned off.
PASS
The ring voltage was successfully detected. 
NO
BOARD
Power supply is administered but not detected.
1. Verify that the power supply is plugged in.
2. If the power supply was already plugged in, replace the power supply.
1. The values of these failure codes might be added together. For example, a value of 36 indicates that the 
ringer generator is inactive because of a short and that the ring generator has an internal fault.
Table 703: Test 1540 Ring generator status  (continued)
Error
Code
Test
Result
Description / Recommendation