RING-GEN (Analog Ring Generator)
Issue 1 June 2005
1945
 
Analog Ring Generator Query Test (#118)
The Analog Ring Generator Query test requests the active Tone-Clock circuit pack to check the 
ringing voltage. The Tone-Clock circuit pack replies with PASS if the ringing voltage is adequate 
to ring the analog phones. If not, the active Tone-Clock circuit pack replies with a FAIL.
2000
ABRT
Response to the request was not received within the allowable time 
period.
1. Look for TDM-CLK errors and alarms. Resolve every other 
Tone-Clock problem first.
2. Rerun the test.
PASS
The active Tone-Clock has successfully been enabled to monitor the 
ringing voltage level.
Table 715: Test #117 Analog Ring Generator Initialization Test  (continued)
Error
 Code
Test
 Result
Description / Recommendation
 2 of 2
Table 716: Test #118 Analog Ring Generator Query Test 
Error
 Code
Test
 Result
Description / Recommendation
1
1000
1001
1003
1115
2012
2100
ABRT
Could not seize the resources to run the test. Other maintenance is 
running on the active Tone-Clock circuit pack.
1. Wait for the green LED on the active Tone-Clock circuit pack to go out.
2. Use status port-network to determine the active Tone-Clock 
circuit pack.
3. Rerun the test. If the test aborts again, see 
2000
ABRT
Response to the request was not received within the allowable time 
period.
1. Look for TDM-CLK errors and alarms. Resolve every other 
Tone-Clock problem first.
2. Rerun the test.
 1 of 4