SN-CONF (Switch Node Configuration)
Issue 1 June 2005
1993
 
Error Log Entries and Test to Clear Values
Notes:
a. Error Type 0: run the short test sequence first. If every test passes, run the long test 
sequence. Refer to each appropriate test’s description, and follow its recommended 
procedures.
b. Error Type 5000: at least one administered circuit pack in this switch node carrier was not 
inserted, or one or more administered circuit packs in this switch node carrier did not 
respond to Test 760 with a “board insertion” uplink message.
To resolve this error, run test 760 using test board location l for an SNC in the same 
switch node carrier that has this error.
Table 736: SN-CONF Error Log Entries
Error
Type
Aux
Data
Associated Test
Alarm
Level
On/Off
Board
Test to Clear Value
)
0
Any
Any
Any
test board location sh r 1
5000 (
)
Any
Processor Route Audit (#760)
MIN
OFF
test board location l rep 1
6000 (
1
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6000 (
2
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6001 (
)
Any
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6002 (
)
1
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6002 (
)
2
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6003 (
Any
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6004 (
)
Any
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6005 (
)
Any
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6005 (
)
1
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6005 (
)
2
Configuration Audit (#759)
MAJ
OFF
test board location rep 1
6006 (
)
Any
Configuration Audit (#759)
MIN
OFF
test board location rep 1
6007 (
)
Any
Configuration Audit (#759)
MIN
OFF
test board location rep 1