Avaya 03-300430 User Manual

Page of 2574
SN-CONF (Switch Node Configuration)
Issue 1 June 2005
1995
 
h. Error Type 6005: a link does not exist to one of the SNCs. If the Aux Data is not 1 or 2, the 
link from this SNI to the active SNC does not exist. If the Aux Data is 1, the link from this 
SNC to the active SNC does not exist. If the Aux Data is 2, the link from this SNC to the 
standby SNC does not exist.
To resolve this error, refer to FAIL code 112 for the Configuration Audit test (#759).
i. Error Type 6006: the SNI is administered to be connected to a DS1C but is not.
To resolve this error, refer to FAIL code 139 for the Configuration Audit test (#759).
j. Error Type 6007: the SNI is connected to a DS1C, but no DS1C is administered.
To resolve this error, refer to FAIL code 140 for the Configuration Audit test (#759).
System Technician-Demanded Tests:
Descriptions and Error Codes
Investigate tests in the order presented below. Clearing error codes associated with the one test 
may also clear errors generated from other tests in the sequence.
15
115
16
116
17
117
18
118
19
119
20
120
Aux Data 
(slot no.)
Test 759 
FAIL Code
 2 of 2
Order of Investigation
Short Test
Sequence
Long Test
Sequence
Reset Board
Sequence
D/ND
1
1. D = Destructive, ND = Nondestructive
Configuration Audit (#759)
X
X
ND
Processor Route Audit (#760)
X
ND