TIE-DS1 (DS1 Tie Trunk)
Issue 1 June 2005
2289
 
FAIL
The far-end trunk did not respond to the seizure of the near-end trunk 
within the allowable time period. This test could have associated in-line 
errors in the error log.
1. Enter list configuration board location. If the circuit pack 
is a TN767B vintage 8 or 9, a failure of test 136 causes a subsequent 
failure of test 7 due to a firmware bug. Eventually, the board and all of 
its ports are taken out of service, and extraneous on-board alarms are 
generated. Replace the circuit pack with a TN767C V3 or later.
2. Verify that the Trunk Type field on the Trunk Group administration 
form matches the trunk type administered on far-end switch.
3. Look for DS1-BD, UDS1-BD, or MG-DS1 errors in the hardware error 
log. If present, see 
documentation.
4. Retry the test at 1-minute intervals up to 5 times.
2000
FAIL
Response to the seizure message was not received within the allowable 
time period.
1. Enter list configuration board location
For circuit packs: If the circuit pack is a TN767B vintage 8 or 9, a 
failure of test 136 causes a subsequent failure of test 7 due to a 
firmware bug. Eventually, the board and all of its ports are taken out of 
service, and extraneous on-board alarms are generated. Replace the 
circuit pack with a TN767C V3 or later.
G700
: Replace the Media Module.
2. Verify that the Trunk Type field on the Trunk Group administration 
form matches the trunk type administered on far-end switch.
3. Look for DS1-BD, UDS1-BD, or MG-DS1 errors in the hardware error 
log. If present, see the 
documentation.
4. Retry the test at 1-minute intervals up to 5 times.
PASS
The trunk can be seized for an outgoing call.
Table 818: Test #136 DS1 Tie Trunk Seizure Test  (continued)
Error
Code
Test
Result
Description / Recommendation
 4 of 5