Communication Manager Maintenance-Object Repair Procedures
2458 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
2000
ABRT
Response to the test was not received within the allowable time period. This 
may be due to hyperactivity. Error Type 1538 in the error log indicates 
hyperactivity. The hyperactive circuit pack is out of service, and one or more 
of the following symptoms may be exhibited.
The UDS1-BD tests (such as Tests #138 and #139) are aborting with 
Error Code 2000.
The tests run on the ports of this circuit pack are returning a no-board 
result.
busyout or a release command has no effect on the test results.
list config shows that the circuit pack and its ports are 
properly installed.
When hyperactivity occurs, the circuit pack is isolated from the system, and 
all of its trunks are placed into the out-of-service state. The system will try to 
restore the circuit pack within 15 minutes. When no faults are detected for 
15 minutes, the UDS1 interface circuit pack is restored to normal operation. 
Every UDS1 Interface trunk is then returned to the in-service state. 
Hyperactivity is often caused by the associated facility. In such a case, 
faults (such as slips, misframes, or blue alarms) would be entered in the 
error log. In addition, many hardware errors would be logged against the 
associated trunk circuits. If the facility is OK and the error occurs again after 
15 minutes, replace the circuit pack.
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
2
FAIL
The CLJ-LB test failed because it was not set up properly. The UDS1 
interface pack could not successfully put the CPE loopback jack into 
loop-back mode.
1. Rerun test ds1-loop location 
cpe-loopback-jack-test-begin
2. If the test continues to fail, the problem could be with the UDS1-BD 
board, the CPE loopback jack equipment, or somewhere between. 
Run test ds1-loop location ds1/csu-loopback-tests to 
determine whether the loop-back tests that are closer to the UDS1-BD 
board are successful. If any of these tests fail, follow the maintenance 
strategy that is associated with the failing test.
Table 870: Test #1212 CPE Loop-Back Jack Test  (continued)
Error
Code
Test
Result
Description / Recommendation