2462 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
2000
ABRT
Response to the test was not received within the allowable time period. 
This may be due to hyperactivity. Error Type 1538 in the error log 
indicates hyperactivity. The hyperactive circuit pack is out of service, and 
one or more of the following symptoms may be exhibited.
1. The UDS1-BD tests (such as Tests #138 and #139) are aborting with 
Error Code 2000.
2. The tests run on the ports of this circuit pack are returning a no-board 
result.
3. A busyout or a release command has no effect on the test results.
4. A list config shows that the circuit pack and its ports are properly 
installed.
When hyperactivity occurs, the circuit pack is isolated from the system, and 
all of its trunks are placed into the out-of-service state. The system will try 
to restore the circuit pack within 15 minutes. When no faults are detected 
for 15 minutes, the UDS1 interface circuit pack is restored to normal 
operation. Every UDS1 Interface trunk is then returned to the in-service 
state. Hyperactivity is often caused by the associated facility. In such a 
case, faults (such as slips, misframes, or blue alarms) would be entered in 
the error log. In addition, many hardware errors would be logged against 
the associated trunk circuits. If the facility is OK and the error occurs again 
after 15 minutes, replace the circuit pack.
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
2
FAIL
The test failed because it was not set up properly. The UDS1 pack could 
not successfully put the far-end CSU into loop-back mode.
1. Rerun test ds1-loop location 
far-csu-loopback-test-begin.
2. If the test continues to fail, the problem could be with the UDS1-BD 
board, the CPE loopback jack equipment, or somewhere between. 
Run test ds1-loop location 
cpe-loopback-jack-test-begin
 to determine whether the CPE 
loopback jack loop-back test is successful. If a CPE loopback jack 
device is not being used, enter test ds1-loop location ds1/
csu-loopback-tests
 instead. If the closer loop-back test fails, 
follow the maintenance strategy associated with that test.
Table 871: Test #1213 Far CSU Loop-Back Test  (continued)
Error
Code
Test
Result
Description / Recommendation