Avaya 03-300430 User Manual
Communication Manager Maintenance-Object Repair Procedures
2524 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
Error Log Entries and Test to Clear Values
Notes:
a. Error Type 1: the number of VC resources in the system that are in service has fallen below
the calculated minimum value. If the number of in-service VC ports falls below the MMCH
port capacity (value entered in the Minimum Maintenance Threshold VCs field on the
port capacity (value entered in the Minimum Maintenance Threshold VCs field on the
system parameters maintenance screen), a VEC-LEV error is logged.
If this outage continues for 15 minutes a MAJOR alarm is raised. To resolve this alarm,
correct the out-of-service problem:
correct the out-of-service problem:
1. See
on page 2509 to resolve any associated
alarms.
2. If a VC-LEV error/alarm exist and none has been raised against VC-BD or VC-DSPPT
MOs, a VC circuit pack may have been removed from service causing the VC-LEV error/
alarm. To resolve a VC-LEV MAJOR alarm, restore the number of VC ports available for
service to be equal to or more than the calculated port capacity. See
alarm. To resolve a VC-LEV MAJOR alarm, restore the number of VC ports available for
service to be equal to or more than the calculated port capacity. See
on page 2522 for details.
System Technician-Demanded Tests:
Descriptions and Error Code
Descriptions and Error Code
There are no System Technician-Demanded test for VC-LEV.
Table 896: VC-LEV Error Log Entries
Error
Type
Type
Aux
Data
Data
Associated Test
Alarm
Level
Level
On/Off
Board
Board
Test to Clear Value
1 (
)
Any
None
MAJ
OFF