Avaya 03-300430 User Manual

Page of 2574
ALARM-PT (Alarm Port)
Issue 1 June 2005
383
 
PASS
The software and the port processor have the same status.
0
NO 
BOARD
The test could not relate the internal ID to the port (no board). This could 
be due to incorrect translations, no board is inserted, an incorrect board is 
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Enter list 
config, and resolve any problems that are found.
2. If the board was found to be correctly inserted in step 
1
, enter 
busyout board location
3. Enter reset board location
4. Enter release board location
5. Enter test board location long. This should re-establish the 
linkage between the internal ID and the port. If this is not the case, 
dispatch to check to ensure that there is a valid board inserted.
Table 111: Test #36 Station Status and Translation Audits and Updates  (continued)
Error 
Code
Test
Result
Description / Recommendation
 3 of 3