ATM-EI (Expansion Interface Circuit Pack)
Issue 1 June 2005
565
 
ATM Board Time Of Day Update (#1261)
This test is nondestructive.  The ATM circuit pack requires a reference time to do SDH/SONET 
performance monitoring.  This test updates the system time to the board and synchronizes the 
board with the S8700 Multi-Connect system’s clock during initialization, scheduled 
maintenance, and craft long test.
PASS
The ATM-EI board is functioning properly, however this test does not verify 
that the optical portion of the lightwave transceiver is functioning.
0
NO
BOARD
No board was detected by the test.
1. Resolve either wrong board (Error 125) or no board (Error 131) issues, 
if applicable.
2. Check that the board is properly translated and inserted.  If so, check 
for hyperactivity (Error 1538).  If hyperactive, use reset board 
location
.
3. Run the test again.  If it fails, the NCE chip on board could be bad.  
Replace the board and retest.
Table 181: ATM Board Framer Loop-Around Test (#1260) (continued)
Error 
Code
Test 
Result
Description / Recommendation
 5 of 5
Table 182: ATM Board Time Of Day Update (#1261) 
Error 
Code
Test 
Result
Description / Recommendation
2031
FAIL
The attempt to send the message to the ATM-EI circuit pack was not 
successful.
2500
FAIL
Did not send the time-of-day information to the board.
1. Retry the command at 1-minute intervals up to 3 times.
PASS
The ATM-EI circuit pack is successfully updated with system time.
1. If status port-network still indicates that this link is down, it is 
possible that one or both of the ATM-EI circuit packs have been busied 
out.
2. If the link still does not come up, reset one or both ATM-EI circuit 
packs on the link.