Diagnostic Test—Auxiliary Trunk Test (#114)
The system software sends a message to the on-board microprocessor to operate a relay in the
port circuit. If ground is detected, the test passes.
port circuit. If ground is detected, the test passes.
Table 227: Test #114 Diagnostic Test—Auxiliary Trunk Test
Error
Code
Code
Test
Result
Result
Description / Recommendation
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1000
ABRT
System resources required to run this test are not available. The port may
be busy with a valid call.
be busy with a valid call.
1. Use display port location to determine the trunk group/
member number of the port. Use status trunk to determine the
service state of the port. If the port is active, wait until it is idle.
2. Retry the command at 1-minute intervals up to 5 times.
1004
ABRT
The port was seized by a valid call during the test. The test has been
aborted.
aborted.
1. Use display port location to determine the trunk group/
member number of the port. Use status trunk to determine the
service state of the port. If the port is active, wait until it is idle.
2. Retry the command at 1-minute intervals up to 5 times.
2100
ABRT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
This test failed to detect ground.
1. Try the test once more.
2. If the test fails again, replace the circuit pack.
PASS
This test passed. Ground was detected.