Avaya 03-300430 User Manual
CAB-TEMP (Cabinet Temperature)
Issue 1 June 2005
755
Table 260: Test #1537 Power Supply Temperature
Error
code
code
Test
result
result
Description and recommendation
1000
ABRT
There is an internal software error.
1. Repeat the command at one-minute intervals 1 to 3 times.
1035
ABRT
The port network is not available.
1. Use status port-network to verify that the network is not up.
2. Look for alarms against EXP-PN, EXP-INT, PK-INT, etc.
2. Look for alarms against EXP-PN, EXP-INT, PK-INT, etc.
3. Use diagnostic procedures for those MOs to clear the problem.
2028
ABRT
There is a problem communicating with the environmental maintenance
firmware.
2100
ABRT
The system could not allocate resources.
1. Repeat the command at one-minute intervals 1 to 3 times.
2319
ABRT
The EPN is out of range.
2500
ABRT
An internal operation failed.
1. Repeat the command at one-minute intervals 1 to 3 times.
1
FAIL
The inlet temperature is over threshold.
1. Use test board location to check the temperature.
2. If redundant power supplies are present, there may be a problem with
2. If redundant power supplies are present, there may be a problem with
the backplane. Verify that each power supply can detect the problem by
using recycle carrier, specifying the slot number of the power
using recycle carrier, specifying the slot number of the power
supply to be shut down. Refer to the notes and cautions for this
command in Maintenance Commands Reference (03-300191) before
executing recycle carrier.
command in Maintenance Commands Reference (03-300191) before
executing recycle carrier.
3. Replace the power supply.
4. If the problem persists, check the backplane for shorts.
1 of 2