Communication Manager Maintenance-Object Repair Procedures
756 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
2
FAIL
The exhaust temperature is over threshold.
1. Use the test board location command to check the temperature.
2. If redundant power supplies are present, there may be a problem with 
the backplane. Verify that each power supply can detect the problem by 
using recycle carrier, specifying the slot number of the power 
supply to be shut down. Refer to the notes and cautions for this 
command in Maintenance Commands Reference (03-300191) before 
executing recycle carrier.
3. Replace the power supply.
4. If the problem persists, check the backplane for shorts.
3
FAIL
Both the inlet and the exhaust temperatures are over threshold. 
1. Use the test board location command to check the temperature.
2. If redundant power supplies are present, there may be a problem with 
the backplane. Verify that each power supply can detect the problem by 
using recycle carrier, specifying the slot number of the power 
supply to be shut down. Refer to the notes and cautions for this 
command in Maintenance Commands Reference (03-300191) before 
executing recycle carrier.
3. Replace the power supply.
If the problem persists, check the backplane for shorts.
4
FAIL
There is a hot spot temperature warning.
8
FAIL
There is a hot spot temperature shutdown.
PASS
The inlet, exhaust, and hot spot temperatures are within limits. 
NO
BOARD
The power supply is administered but not detected.
1. Verify that the power supply is plugged in.
2. Replace the power supply.
Table 260: Test #1537 Power Supply Temperature  (continued)
Error 
code
Test 
result
Description and recommendation
 2 of 2