Communication Manager Maintenance-Object Repair Procedures
760 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
CMC1
Notes: 
a. Error Type 0: Run the Short Test Sequence first. If all tests pass, run the Long Test 
Sequence. Refer to the appropriate test description and follow the recommended 
procedures.
b. Error Type 1: the Power/Fan Status lead indicates that the power supply of one or more 
CMC1 cabinets has detected an alarm condition. The condition can be caused by the failure 
of any fan or the failure of any power supply output. If more than one CMC1 cabinet exists, 
all of the Power/Fan Status leads are tied together (the fan and power lead is an O-ring of all 
cabinets’ status leads). Since an error condition on a fan or power supply output could be 
the result of a temporary overload (e.g. during board insertion) or caused by the location of 
the equipment (e.g. fan blockage), a single event may be an anomaly that eventually clears. 
However, a repeating condition will cause a major alarm.
c. Error Type 257: temperature Sensor 1: Since temperature alarms can be transient, a single 
event may be an anomaly that eventually clears. However, a repeating condition will cause 
a major alarm and may indicate a need to replace one or more components (e.g. a Cabinet 
Fan may be bad, or check to see if the equipment room air conditioning supply/unit is 
functional).
d. Error Type 513: temperature Sensor 2: Since temperature alarms can be transient a single 
event may be an anomaly that eventually clears. However, a repeating condition will cause 
a major alarm and may indicate a need to replace one or more components (e.g. a Cabinet 
Fan may be bad, or check to see if the equipment room air conditioning supply/unit is 
functional).
Table 263:
CMC1
: Cabinet sensors error log entries 
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
)
0
Any
Any
Any
test environment
1(
)
257 (
)
513 (
769 (
1025 (
1281 (
1537 (
1793 (
)
Any
Cabinet 
Temperature or 
Voltage Query 
Test (#122)
MAJ
ON
test environment