Avaya 03-300430 User Manual
Communication Manager Maintenance-Object Repair Procedures
766 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
S8700 |
8710
S8500
:1
(
cont’d
)
FAIL
(
(
cont’d
)
If some of the fans are running and some are not:
1. Replace the defective fans. If every fan can then be started, wait 5
minutes and rerun the test. If the test fails again, proceed to the next
step.
step.
2. Remove all six white 5-pin connectors on the front and back of the fan
assembly. This will cause every fan to run at high speed and the alarm
to be cleared.
to be cleared.
S8700 MC
: If the alarm does not clear, a PN’s Maintenance circuit pack
is incorrectly reporting the problem. Check for and resolve every error
against MAINT, and then rerun the test.
against MAINT, and then rerun the test.
3. One at a time, replace the 5-pin connectors and check to see if the
alarm recurs. Replace each fan whose reconnection causes a
recurrence of the alarm.
recurrence of the alarm.
Table 264: Test #122 Cabinet Temperature Query Test (continued)
Error
Code
Code
Test
Result
Result
Description / Recommendation
4 of 7