Communication Manager Maintenance-Object Repair Procedures
768 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
S8700 | 
8710
 
S8500
:1
(cont’d)
FAIL
(
cont’d
)
NONVARIABLE-SPEEDFAN ASSEMBLIES (cont’d): If the fans are 
running at high speed, check the following items, any of which can restrict 
or redirect airflow within the cabinet.
1. Check both filters.  If a filter is dirty or clogged, clean with soapy water 
or a vacuum.
2. Ensure that there is nothing other than circuit packs in the carrier slots 
that could be restricting the airflow.
3. Ensure that there are no missing circuit-pack faceplates or blanks.
4. The cabinet door must be closed for proper cooling.
5. Wait 5 minutes for the cabinet to cool and rerun the test.
6. If the test fails, check temperatures for the 15
0
-/50
0
-C criteria.  If the 
15
0
-/50
0
-C criteria is present, then the fans should be running at high 
speed.
7. Wait 5 minutes, and rerun the test.
8. If the test still fails, then the ambient room temperature is probably too 
high.  Cool the room.
9. If the 15
0
-/50
0
-C criteria does not exist, one of the following 
components if defective:
AHD1 circuit pack
fans
S3 sensors
S4 sensors
Replace these items one at a time in the order listed, running the test 
after each replacement. 
S8700 MC
: If many environmental tests are failing, it can be a problem 
that is undetected by maintenance on a PN’s Maintenance circuit pack.  
Replace the circuit pack.  
Escalate if the problem persists.
Table 264: Test #122 Cabinet Temperature Query Test  (continued)
Error 
Code
Test 
Result
Description / Recommendation
 6 of 7