Communication Manager Maintenance-Object Repair Procedures
780 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
The table below shows what carriers are protected by each circuit breaker on the J58890CH-1.  
The ring generator is protected by a fuse located next to the main circuit breaker on the front of 
the unit.
Neon Lamp Power
The system can also support neon message waiting lamps on analog telephones.  Any carrier 
containing a TN769 Neon Analog Line circuit packs must also be supplied with 150 Volts from a 
TN755B power supply circuit pack.  See the table above for other supported neon power circuit 
packs.
Error Log Entries and Test to Clear Values
!
WARNING:
WARNING:
The OLS Recycle test (#126) is destructive.  For more information, se
Circuit Breaker Associated Carriers
CB1
Carrier A, both sides
CB2
Carrier B, both sides
CB3
Carrier C, both sides
CB4
Carrier D, both sides
CB5
Carrier E, both sides
CB6
 Level F (Fans) and Level G (Ring Generator)
Table 266: Carrier Port Power Supply Error Log Entries
Error 
Type
Aux 
Data
Associated Test
Alarm 
Level
On/Off 
Board
Test to Clear Value
1
1
1. Run the OLS Query test (#127) using  test environment UU r 2.  If a carrier must be recycled to clear the 
CARR-POW alarm, use recycle carrier UUC to run the OLS Recycle test (#126).  The OLS Recycle test 
(#126) is not included in either the long or short test sequences.
0 or 1
OLS Query test (#127)
MAJ
ON
test environment UU r 2
recycle carrier UUC