Server Alarms
92 Maintenance Procedures for Avaya Communication Manager 3.0, Media Gateways and Servers
 
1. These events will degrade the server’s state of health.
System Technician-Demanded Tests:
Descriptions and Error Codes
This MO provides no on-demand tests for system technicians.
Back to:              
             
UPS Alarms to the Media Server
S8700 | 8710
 / 
S8500
 / 
S8300
alarms and their troubleshooting procedures.
Trap (3) – 
upsAlarmGeneralFault
#1,ACT,UPS,A,27,WRN,Miscellaneous trap, e.g., bad 
battery
(For troubleshooting procedures, see Event #
Table 25: Enterprise-Specific UPS Traps to Server  (continued)
SNMP Trap from UPS
Event
ID
Definition of Trap
 4 of 4
Table 26: UPS Alarms to the Media Server 
Event
ID
Alarm
Level
Alarm Text, Cause/Description, Recommendation
1–8
MAJ
“upsEstimatedMinutesRemaining” — UPS does not have an AC-power 
source.
1. Restore AC power to the UPS.
12
MAJ
“upsAlarmShutdownPending” — A shutdown-after-delay countdown is 
underway (i.e., the UPS has been commanded off).
1. Stop countdown timer. (Can be done via SNMP messages.)
13
MAJ
“upsAlarmShutdownImminent” — The UPS will turn off power to the load in 
< 5 seconds.
1. Restore AC power to the UPS.