3.4 Trigger input connections
Figure 3.4
Message sequences or announcements are started with make contacts (17). These make contacts are connected to 
the trigger input screw terminals (11). The cabling of the first six trigger input contacts (1 through 6) can have 
supervision by means of a window comparator. Normal operation of these inputs requires two series connected 
resistors of 10 kOhm and 3.3 kOhm, permanently connected to the far end of the cable connected to each trigger 
input. Triggering occurs by short-circuiting the 10 kOhm resistor as shown in figure 3.4.
Open or short-circuited cables to such an input result in a fault situation that is detected by the window comparator. 
The fault indicator LED at the front will light up and the internal fault relay will be unpowered which gives a 
contact change on the screw terminals (10) at the rear.
Via the dipswitches 1 through 6 at the rear of the unit supervision of each individual trigger input (1 - 6) can be 
enabled ('ON') or disabled ('OFF'). When disabled these inputs act the same as inputs 7 through 12.
Via dipswitch # 7 it is possible to enable mains failure checking. When enabled ('ON') the fault indicator LED at the 
front will light up and the internal fault relay will go to the unpowered state upon mains failure, although the unit 
may continue to work on the 24 Vdc battery. 
When disabled ('OFF') switching between mains and battery operation is automatic and will not be noticed.
Via dipswitch # 8 it is possible to switch ON a 20 kHz pilot tone to the output signal for supervision of the cable by 
connecting equipment. The level of the pilot tone is adjustable (from 'OFF' to -14dB with respect to maximum audio 
level) via the pilot tone volume control (1). The default volume level is -20 dB.
External settings and connections
+
Pilot Message
Tone
Loop through
Supervision
Pilottone
Msg Active
Trigger Input
RS232 to LBB1925
Rated Input
Power:50VA
To.5L250V
RS232 to PC
WK
S/N
Mains
OFF
NC
NO
NO
1
2
3
4
5
6
8
9
10
11
12
7
C
NC
24V
Fault
GND
C
ON
Trigger Input 1-6
1 2 3 4 5 6 7 8
In
In
Out
Out
LBB 1965/00
8900 196 5005
115V~
230V~ 50/60Hz
Apparatus delivered connected for
230V~
This apparatus must be earthed
Warning
1
11
10
10k
Ω
3.3k
Ω
17