D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1
EN | 115
Bosch Security Systems | 1/04 | 47775E
6.0
RADXAUX1
6.1
Introduction
The RADXAUX1 Handler is primarily used for
programming Enhanced Communication capabilities
for the 9000 Series Control Panels. As new features
(that require new programmable prompts) are
added, they will most likely be added to a new
revision of this handler.
“Enhanced communications” represents the ability
to provide new communication functions for the
control panels using the SDI bus including:
 
Routing control panel events to a D9133TTL-x
module.
 
Communicating with RPS using a D9133TTL-x
module.
 
Communicating with a remote or local head-end
software package.
6.2
RPS and D5200 Handler
Requirements
In order to program the RADXAUX1 parameters
for the control panels, you must use RPS version 2.8
or higher and a handler called RADXAUX1. To
add the RADXAUX1 Handler to your D5200
Programmer, call the Bosch Security Systems
Handler Update System at (800) 657-4584.
This handler currently has six sections: SDI
Automation, SDI RAM Parameters, Enhanced
Communications, SDI RAM/Enhanced
Communication Configuration, Miscellaneous, and
Cross Point Parameters. The D5200 Handler
required for these options is found in the
RADXAUX1 Handler version 1.0 and is available
on the Handler Update System at Bosch Security
Systems.
6.3
SDI Automation
Define the characteristics of the D9133 Serial
Interface Module when used with Home or Business
Automation software. The D9133 Serial Interface
Module is a bi-directional SDI to RS-232 Interface
Module that allows the control panels to
send/receive information to/from an external
software program. This Automation protocol allows
external software programs to interact and perform
functions such as: arming and disarming areas,
changing user passcodes and names, and turning
relays on and off. The following items allow some
simple configuration options; however, to receive
the D9133 Automation protocol you must contact
Bosch Security Systems Technical Support at 888-
886-6189.
Enable SDI Auto
Default:
No
Selection:
Yes or No
Yes
Enable Automation software.
No
Disable Automation software.
Turning this item to Yes enables the automation
address (SDI Address 80).
Baud Rate
Default:
9600
Selection:
300, 1200, 2400, 4800, 9600, 14.4 K
This item determines the baud rate between the
D9133 and the external hardware connected to it.
Since the SDI bus communicates at 9600 baud,
Bosch Security Systems recommends that this
prompt also be kept at 9600 baud. Pressing the
[SPACE] bar on the D5200 toggles through the
available options.
Parity/Stop
Default:
No/1
Selection:
No/1, No/2, Odd/1, Even/1
No/1
No parity, 1 stop bit
No/2
No parity, 2 stop bits
Odd/1
Odd parity, 1 stop bit
Even/1
Even parity, 1 stop bit
This prompt addresses two items: Parity and the
number of stop bits. Pressing the [SPACE] bar on
the D5200 toggles through the available options.