When configuring this item to allow for
local programming, the D9133 needs
Jumper 8 shorted, power must be cycled
after changing the address, and a standard
serial modem cable is required.
Call Back Enabled
Default:
No
Selection:
Yes or No
Yes
When the control panel hears the
proper RAM password (see 
RAM
Passcode
 in Section 2.7 RAM
Parameters), it ends the SDI RAM
session and then attempts to reconnect
to RAM using the RAM IP Address if
Enable Ext Modem
 is set to No. If
Enable Ext Modem
 is set to Yes, the
control panel attempts to re-establish
communication with RAM using the
RAM Dial String. This ensures that the
control panel only communicates with
valid RAM units.
No
The SDI RAM session is initiated
immediately; no call back is required.
The control panel can engage in SDI
RAM sessions regardless of originating
location.
Using this function allows the control panel, after
verifying the RAM passcode, to provide an
additional level of security. Before allowing any
upload or download, it ends the SDI RAM session
and then reconnects with RAM using one of the
following:
 
The RAM IP Address (
Enable Ext Modem
must be set to No)
 
The RAM Dial String (
Enable Ext Modem
must be set to Yes)
In firmware version 6.30, do not enable
RAM Call Back when using an external
modem.
RAM IP Address 1
Default:
0
Selection:
0 to 255
0 to 255
Enter the first three digits of the IP
address. If the field is one or two digits
in length, leading zeros are not
required.
This prompt and the next three prompts determine
the IP address for RPS.
An IP address consists of four fields. Each field has a
range of 0 to 255. For example, an IP address is
expressed as 110.227.64.190. The D5200
programmer splits the IP Address into four
programmable fields. Be sure you contact your
network administrator to find out the IP address to
which the RPS computer is connected.
Figure 6: RAM IP Address Prompts
110.227.64.190
RAM IP Address 1
RAM IP Address 2
RAM IP Address 3
RAM IP Address 4
Set this item to 0 if Enable Ext Modem is
set to Yes.
RAM IP Address 2
Default:
0
Selection:
0 to 255
See 
RAM IP Address 1
.
RAM IP Address 3
Default:
0
Selection:
0 to 255
See 
RAM IP Address 1
.
RAM IP Address 4
Default:
0
Selection:
0 to 255
See 
RAM IP Address 1
.
6.4.2
Using an External Modem
Through the use of a standard, off-the-shelf modem
(capable of communicating at 9600 baud) and a
D9133DC connected directly to the control panel,
RPS can now communicate with a 9000 Series
Control Panel (version 6.3 or higher) at speeds of up
to 9600 baud.