D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1
EN | 129
Bosch Security Systems | 1/04 | 47775E
Conversely, if a single Cross Point detects an alarm,
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A
second alarm on the first point does not create an
Alarm Event but rather an Unverified Event.
Section 2.3 Routing determines whether these events
are transmitted to a central station. An Unverified
Event does not produce a corresponding Restoral
Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or
trouble conditions. Points programmed with point
response D (Delayed) eventually go into an alarm
condition if the area is not disarmed in time.
Use the Cross Point function on Non-fire
points only.
Cross Point Time
Default:
20 seconds
Selection:
5 seconds to 255 seconds
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.