Bosch D7412G User Manual
D9412G/D7412G | Program Entry Guide | 6.0 RADXAUX1
EN | 129
Bosch Security Systems | 1/04 | 47775E
Conversely, if a single Cross Point detects an alarm,
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A
second alarm on the first point does not create an
Alarm Event but rather an Unverified Event.
then restores, and no other conditions occur, an
Unverified Event is generated for that point. A
second alarm on the first point does not create an
Alarm Event but rather an Unverified Event.
Section 2.3 Routing determines whether these events
are transmitted to a central station. An Unverified
Event does not produce a corresponding Restoral
Event.
are transmitted to a central station. An Unverified
Event does not produce a corresponding Restoral
Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or
trouble conditions. Points programmed with point
response D (Delayed) eventually go into an alarm
condition if the area is not disarmed in time.
conditions. It does not apply to supervisory or
trouble conditions. Points programmed with point
response D (Delayed) eventually go into an alarm
condition if the area is not disarmed in time.
Use the Cross Point function on Non-fire
points only.
points only.
Cross Point Time
Default:
20 seconds
Selection:
5 seconds to 255 seconds
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.
within a Cross Point Group are in alarm before a
Cross Point event is generated.