Bosch D7412G User Manual

Page of 142
D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 14
Bosch Security Systems | 1/04 | 47775E
Phone Supv Time
Default:
Blank
Selection:
Blank or 10 to 240
Blank
No phone line supervision.
10 to 240
Enter the number of seconds (in 10
second increments) you wish to
supervise the phone line. After a faulted
phone line restores, it takes the same
amount of time to initiate restoral
responses.
Phone line trouble responses: Command centers
display 
SERVC PH LINE #
 to indicate which
phone line failed. The command center initiates a
trouble tone if 
Buzz on Fail
 is Yes and 
CC Trouble
Tone
 is Yes.
With dual phone lines (using the D928 Module), the
restored phone line handles all messages regardless
of the phone line’s number.
Phone, Trouble, and Restoral Events report when
they occur. They report also when a Diagnostic
Report is initiated from a command center or by a
Sked.
Alarm On Fail
Default:
No
Selection:
Yes or No
Yes
Generate alarm responses when a
phone line fails.
No
Phone failures report as trouble
responses for Area 1 and/or the
account number for Area 1.
0101
0101
0101
Phone Supv Time must be programmed to
use this feature.
Phone Failure Alarm Responses: The
Alarm Bell relay for Area 1 activates. All
Phone Event messages report as Area 1
and/or the account number for Area 1.
Buzz on Fail
Default:
No
Selection:
Yes or No
Yes
Generate panel-wide trouble tones and
display 
PHONE FAIL #
 at command
centers when a Phone Fail Event
occurs.
No
Does not generate trouble tones at
command centers when a Phone Fail
Event occurs. 
PHONE FAIL #
 still
displays.
0101
0101
0101
Phone Supv Time must be programmed to
use this feature.
De-selecting individual command
centers for panel-wide trouble tones:
Panel-wide trouble tones for programming
CC can turn off individual command
centers (based on their CC # 1 through 8)
# Trouble Tone in Command Center
Parameters as No.
Two Phone Lines
Default:
No
Selection:
Yes or No
Yes
The D928 Dual Phone Line Module is
installed. The LEDs on the D928 light
to indicate primary or secondary line
trouble and COMM FAIL.
No
No D928 Dual Phone Line Module.
Use this program item when a D928 Dual Phone
Line Module is connected to the control panel. Both
lines must operate the same; either ground start or
loop start.
0101
0101
0101
IMPORTANT! Program Phone Supv Time
when using two phone lines.
NFPA standards prohibit the use of ground
start phone lines in systems monitoring
Fire points.