D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 60
Bosch Security Systems | 1/04 | 47775E
L## Perim Instant
Default:
See 
Program Record Sheet
Selection:
Blank or E
#4 Perimeter Instant Arm [COMMAND][2]
Instant arm all Perimeter points, including Delayed
points, only in the area where the command center
is assigned.
L## Perim Delay
Default:
See 
Program Record Sheet
Selection:
Blank or E
#5 Perimeter Delay Arm [COMMAND][3]
Delay arm all Perimeter Delay point responses only
in the area where the command center is assigned.
L## Watch Mode
Default:
See 
Program Record Sheet
Selection:
Blank or E
#6 Watch Mode [COMMAND][6]
Initiate the Watch Mode in the area to which this
command center is assigned.
L## Perim Partial
Default:
See 
Program Record Sheet
Selection:
Blank or E
#7 Perimeter Partial Arm [COMMAND][8]
Partially arms only the area where the command
center is assigned.
This function ignores the A# FA Bypass
Max
 entry in Area Parameters.
0101
0101
0101
Local Only Reporting:  No Closing
Report is sent to the central station, but a
Perimeter Delay Closing Event is
generated in the event log.
L## View Area Stat
Default:
See 
Program Record Sheet
Selection:
Blank or E
#8 View Area Status (MENU FUNCTION only)
View the current arm/disarm and not ready to arm
status of all areas within the scope of the command
center in this area. The user needs arming/disarming
authority.
L## View Memory
Default:
See 
Program Record Sheet
Selection:
Blank or E
#9 View Event Memory [COMMAND][4][0]
View all memory events that occurred since the last
time the system was armed for all areas within the
scope of the command center in this area.
L## View Pt Status
Default:
See 
Program Record Sheet
Selection:
Blank or E
#10 View Point Status (MENU FUNCTION only)
View the current status of all points in the area to
which this command center is assigned.
L## Walk Test
Default:
See 
Program Record Sheet
Selection:
Blank or E
#11 Walk Test [COMMAND][4][4]
Initiate a Walk Test for all Interior/Perimeter
Controlled points in the area to which this command
center is assigned.
The following features are provided with the Walk
Test Mode:
 
During this test, the battery powers the control
panel only. A Battery Test is initiated during the
full duration of the test to ensure the battery
capacity is capable of supporting the full load of
the control panel while AC is failed.
This test includes an initial 2-second Bell
Test when starting the Walk Test.
The test ends once all points are tested or
until the test times out after 20 minutes of
no activity.
 
Local alarm annunciation and event printing
without reporting to the central station receiver.
 
D1255 command center displays a sequential
count after each point is activated and restored
as well as the text for the point.
 
The command center displays 
ALL PTS
TESTED
 and an All Points Tested Event is
reported to the central station receiver (if
programmed) when the last point is tested.
 
If enabled in Routing, Walk Start and Walk End
are reported at the central station receiver for
the beginning and end of the test.