D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
EN | 72
Bosch Security Systems | 1/04 | 47775E
Comm Fail
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
This relay activates when a control panel is unable
to communicate a report after making ten attempts
to each routing destination. At the same time, 
COMM
FAIL RT ##
 displays at the command center. This
relay automatically resets when a report is sent
successfully.
Use this relay to report primary digital
report failure to an alternate
communication device.
Log % Full
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Enter the number of the relay that activates when
the log reaches the programmed percentage of its
capacity as programmed in RAM Parameters
program item Log % Full. This relay provides a
steady output until a Get Log and Set Pointer is
performed from the RPS.
Summary Fire
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Enter the number of the relay that activates when
any Fire point in the system (
P## Type 0
P## Fire
Yes) goes into alarm. This relay provides a steady
output until all Fire points in the system are returned
to normal.
Summary Alarm
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Enter the relay’s number that activates when a Non-
fire point goes into alarm. This relay provides a
steady output until the alarm is acknowledged by a
valid passcode then cleared from alarm memory
with an acknowledgment at the command center.
This relay does not activate for silent
alarms.
Summary Fire Tbl
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
This relay activates when any Fire point in the
control panel is in trouble, or if a Fire Supervision
point is missing. This relay provides a steady output
until all Fire points restore to a normal condition.
Summary SupFire
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off
normal). This relay provides a steady output until all
Fire Supervisory points are restored to a normal
condition.
Summary Trouble
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when any Non-fire point in the control
panel is in a trouble condition. This relay provides a
steady output until the user at the command center
acknowledges the trouble.
Summary SupBurg
Default:
Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when any Non-fire Supervisory point in
the control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay
provides a steady output until it is acknowledged at
the command center.