Alarm Relay Response
EN | 43
15.7 Alarm Relay Response
Allegiant alarm responses include the ability to trigger isolated alarm relay outputs 
from an LTC 8540/00 Alarm Interface unit. An alarm output is typically used to 
activate the alarm input of a security Digital Video Recorder (DVR) or other alert-
ing device. In this type of scenario, a DVR is programmed to change recording 
speeds from a slower rate to a faster rate upon alarm activation. Operation of the 
relay outputs from the LTC 8540 Alarm Interface unit depends on the system con-
figuration for responding to alarm events. The alarm output relays behave according 
to the following conditions: 
1.
Relay 1 activates if the system uses the Basic alarm response mode and an alarm 
occurs on any system monitor. Relay 1 deactivates after all alarms have been 
removed from the inputs. Relay 1 also deactivates if the system (monitor or 
alarms) is disarmed by an operator via the keyboard. Pressing [Acknowledge] 
on the system keyboard does not deactivate Relay 1 since the alarm video fol-
lows the contact applied to the unit in this alarm response mode. Other relays 
are not used in this mode.
2.
Relay 1 activates if the base system is set to use the Sequence & Display alarm 
response mode and an alarm occurs on any system monitor. Relay 1 deactivates 
after all alarm videos have been acknowledged (by pressing the [Acknowledge] 
key) via system operator(s) from all system monitors. Relay 1 also deactivates if 
the system is disarmed (either the monitor or the alarm(s)) by an operator via 
the keyboard. Removal of the alarm input does not deactivate Relay 1 since the 
alarm video(s) are not dependent on duration of the contact applied to the unit 
in this alarm response mode. Other relays are not used in this mode.
3.
If the base system uses the Autobuild alarm response mode and an alarm occurs 
on system monitors, the relay corresponding to the monitor number activates 
for the duration that the corresponding alarm input is applied to the unit. The 
relay deactivates if the monitor associated with the relay or if the alarm(s) being 
displayed on the monitor is disarmed by an operator via the keyboard. Pressing 
[Acknowledge] on the system keyboard does not deactivate the relays since the 
alarm video follows the contact applied to the unit in this alarm response mode.
4.
If the Alarm Group table screen, in the PC- based LTC 8059/00 MCS package 
or the LTC 8850/00 GUI Software, contains an alarm group that includes mon-
itors and the monitor option has been selected in the Relay Action column, the 
corresponding relay activates for the duration the alarm video remains on the 
monitor. The relay deactivates if the associated monitor (or the alarm(s) being 
displayed on the monitor) is disarmed by an operator via the keyboard. Pressing 
[Acknowledge] on the system keyboard does not deactivate the relay unless this 
feature has been selected for the associated alarm group. If the Monitor option 
has been set to 1 in the group table, only Relay 1 activates when monitors in 
that alarm group become alarmed.