Praesideo 3.5 | Installation and User Instructions | 3 | Control Equipment
en | 114
6.6 Configuration and operation
6.6.1
Introduction
The next sections give descriptions of the possible 
configuration options. Each description is followed by 
the relevant menu items with detailed instructions per 
menu option. The default values are indicated by an 
asterisk (*) when applicable.
6.6.2
Start-up
When the audio expander is (re)started, the display 
shows the name of the unit. If it shows Load Unit 
Software
, the unit does not contain any firmware or 
contains DCN Next Generation firmware. DCN Next 
Generation firmware must be replaced by Praesideo 
firmware (see section 36.5).
6.6.3
Status screens
The status screens (see table 6.5) provide general 
information about the status of the audio expander.
6.6.4
Fault status
If there is an active fault, the Name screen also shows the 
fault status (see table 6.6). If there is more than one 
active fault, only the most severe fault is shown. A fault 
status only provides global information. The exact 
source of a fault can be found out using the fault events 
list in this manual (see chapter 52).
6.6.5
Main menu
The Menu ... item (see figure 6.9) provides access to the 
main menu.
 
table 6.5: Status screens
Menu Item
Description
Name
Shows the name of the unit and 
(possibly) its fault event status (see 
section 6.6.4).
VU Meter
Visual indication of the signal strengths 
on all audio inputs and audio outputs 
of the audio expander.
table 6.6: Fault status (high to low)
Fault status
Description
No network
The optical network is not 
available.
Fault: Input CIn
Fault in control input n.
(If n = +, faults in multiple control 
inputs.)
Fault: Input AIn
Fault in audio line input n.
(If n = +, faults in multiple audio 
inputs.)
table 6.7: Main menus
Menu item
Description
1 Monitoring
Go to the Monitoring submenu. 
See section 6.6.6.
2 Setup
Go to the Setup submenu. See 
section 6.6.7 (and further).