Praesideo 3.5 | Installation and User Instructions | Emergency Sound Systems
en | 13
Emergency Sound Systems
Bosch Security Systems has made a great effort for the design and manufacturing of the components and also 
supplies all documentation that enables the assembly of a safe and high quality emergency unit in accordance with 
EN60849:1998, EN54-16:2008 and ISO7240-16:2007. Bosch Security Systems has made up this list of requirements, 
based on the standard, which needs to be filled in and subsequently signed off by both parties. The signed paper has 
the nature of a certificate and can have significant meaning in the case of a legal investigation of the liability issue for 
personal injuries.
The safety of the system in accordance with EN60849:1998, EN54-16:2008 and 
ISO7240-16:2007 in an alarm and emergency application does not only depend on component safety, but also 
highly on the installation engineer and the operator. For example, the sound pressure level of the system depends 
on the installation. Moreover, the system should only be installed and operated by qualified personnel.
Modifications of the system should only be executed by authorized persons in accordance with the safety 
concept and need to be registered in the system documentation.
If third party components (not delivered by Bosch Security Systems) are added to the minimal configuration of 
Praesideo, then the EN60849:1998, EN54-16:2008 and ISO7240-16:2007 certification becomes expired.
Only use Power Supply Equipment that is compliant to the current standards and legislation in combination with 
the Praesideo system. Within Europe the Power Supply Equipment shall be EN54-4 compliant.
The end-user must maintain a journal for the system.
In case continuous event logging (beyond the possibilities and capacity provided by the Network Controller) is 
required, the end-user/installer must use the Praesideo system in combination with a logging PC. In that case the 
logging PC is considered as a basic element of the system.
The installer is responsible for security measures to prevent improper use of the system via the Internet and local 
wired or wireless networks.
Bosch Security Systems refuses any liability for damage that might result from non-observance of these 
instructions.
Herewith the undersigned states that he/she has processed for him/her applicable requirements, as specified in this 
document, in an adequate way and has confirmed this fact by signing the rightmost column of each applicable 
requirement.
Installer
Name:
Signature:
Date:
Place:
End-user
Name:
Signature:
Date:
Place: